Bug in Firmware Versions 04.02.25 and Above Causes Transmitter Lockup
Bug in Firmware Versions 04.02.25 and Above Causes Transmitter Lockup
Document:
Description:
Firmware Version 04.02.25 and above contain a bug that will cause the transmitter to lockup and not function if the displayed value for flow rate is greater than five digits (expressed as an exponential number; for example, 2.4e05). This is most likely to be seen with large diameter pipes and units of measure that result in large numbers.
Reference number:
TB021
Asset type:
Technical Bulletin